176 Deg Linear Heat Sensing Cable

PATOL 176 Deg Linear Heat Sensing Cable – Reliable Continuous Heat Detection

The PATOL 176 Deg Digital Linear Heat Sensing (LHS) Cable is specifically designed for extreme-temperature environments where standard heat detection solutions are ineffective or unreliable. With a fixed alarm activation temperature of 176 Deg , this digital linear heat detection cable provides continuous temperature monitoring along its entire length, ensuring dependable fire detection in the most demanding industrial conditions.

This advanced digital LHS solution not only detects abnormal heat but also delivers accurate alarm location information, enabling rapid, targeted firefighting response and reduced operational downtime.

Digital Detection Principle

he PATOL 176 Deg digital LHS cable is constructed using two conductors separated by a specially formulated temperature-sensitive polymer. Under normal conditions, the conductors remain electrically isolated. When the surrounding temperature reaches 176 Deg, the insulation softens at the affected point, allowing conductor contact and triggering an alarm. The connected digital evaluation unit identifies the exact distance to the alarm point, providing precise fire location data.

Key Features & Advantages

  • Fixed alarm temperature of 176 Deg for extreme heat environments

  • Digital addressable technology with precise fire location indication/b>

  • Continuous linear detection across long cable runs

  • High resistance to dust, moisture, vibration, and aggressive industrial atmospheres

  • Stable performance with minimal false alarms

  • Compatible with digital linear heat detection modules and fire alarm systems

Ideal Applications

The PATOL176 Deg Digital Linear Heat Sensing Cable is well suited for installations where very high ambient temperatures are expected, including:

  • Steel plants, foundries, and metal processing facilities

  • Tunnels, shafts, and confined industrial spaces

  • High-temperature conveyor belts

  • Power generation and heavy manufacturing plants

  • Petrochemical and process industry zones


DIGITAL LINEAR HEAT SENSING CABLE 176 Deg C
Type Digital Linear Heat Sensing Cable
Voltage Rating 100Vdc (Dielectric Test 500Vdc)
Maximum Ambient Temperature 105 Degree Centigrade
Minimum Alarm Temperature 176 Degree Centigrade
Maximum Alarm Temperature 176 Degree Centigrade
Number of Cores 2 (Two)
Maximum Conductor Resistance per KM @ 20°C 100 Ohms per KM
Material
Conductor Tinned Copper Coated Steel
Insulation Black & White
Outer Sheath PVC (Red)
Conductor Diameter 0.9 MM
Insulation Material Thickness 0.25 MM
Approval FM Approved
Approximate Detection Time (Small flame) 20 sec (Flame touching)
Life Expectancy / Service Life 20 Years Plus
SS Braiding Available YES (Optional)